AP1280 & AP1290 Field Configurable Limit Alarm

Brand: Eurotherm

Action Pak models AP1280 and AP1290 limit alarms offer wide ranging inputs and flexible setpoint capability.

They accept six popular thermocouple types with inputs ranging from -270° to 1760° C (-454° to 3,200° F). The AP1280 provides a single-setpoint alarm while the AP1290 provides two independent setpoint alarms.

The AP1280 and AP1290 also include 0.25 to 50% adjustable deadbands and selectable 120 / 240 Vac power.
Features
  • Field configurable input ranges for E, J, K, R, S and T type thermocouples
  • Exclusive "Dynamic Deadband" prevents false trips
  • Burnout detection
  • Setpoints programmable HI or LO
  • Selectable failsafe/latching operation
  • Selectable 120 / 240 Vac input power (9 to 30 Vdc available)

Specifications

Brand

Approvals & Certifications

  • CSA C22.2, No. 0-M1982, (File No. LR42272-8,9)
  • IEC 801-2
  • UL (C,US)
  • UL 508 (File No. E99775)

Response Time

  • < 250 Milisecond

Limit Differential

  • 0.25 % to 50 % of Span

Stability

  • Line Voltage: ± 0.01 %/ % Maimum
  • Temperature: ± 0.05 % of Full Scale/°C Max.

Temperature Range

  • 0° C to 60° C
  • 32° F to 140° F
show more