Maximum PV Array Open Circuit Voltage
Maximum Array Short-Circuit Current
- 32 A (25.6 A @ STC) x 2 Channels
Maximum and Minimum PV Input/Output Wire Size
- #6 AWG to #14 AWG (13.5 to 2.5 mm²)
Control Power Input
- 48 Vdc nominal (22-60 Vdc)
PV Disconnect
- 2-Channel, 4 pole DC disconnect switch
Arc Fault Circuit Protection
Rapid Shutdown
- PLC transmitter included, Rapid Shutdown Initiator Switch ordered separately
Product Dimensions (H x W x D)
- 36.8 x 22 x 14.5 cm (14.48 x 8.66 x 5.7 in)
Shipping Dimensions (H x W x D)
- 28.5 x 44.0 x 29.0 cm (11.22 x 17.32 x 11.41 in)
Ambient Air Temperature for Operation
- -20° C to +50° C (-4° F to 122° F)
Operating Altitude
- Sea level to 2000 m (6562 ft)
Safety
- UL 1741, UL 1741 CRD - PV Rapid Shutdown Systems (PVRSS), UL 1699B, CSA C22.2 No. 107.1-16, CSA C22.2 No. 292-18, CSA (LTR) No. AE-004-2015
EMC
- FCC and Industry Canada (Class B)