Model AP4001, AP4041, AP4151 Signal Conditioner

Brand: Eurotherm

Action Pak models AP4001, AP4041 and AP4151 are useful in any application requiring a DC output from an RTD input. 

Typical applications include energy management and data acquisition of process temperatures. 

The output of a 4000 series RTD signal condi-tioner can drive a digital meter for direct display, or interface with a computer for monitoring and control.
Features
  • Provides a DC output in proportion to an RTD input
  • Direct RTD input
  • Integral lead-length compensation
  • Temperature control/monitoring applications
  • Easy plug-in installation/low mean-time-to-repair
  • AC Line powered (DC Optional)

Specifications

Brand

Accuracy

  • AP4151: ± 0.1 % of Span Typical (Referred to Temperature Input)

Approvals & Certifications

  • CSA

Consumption

  • Power Consumption: 3 W Typical
  • Power Consumption: 5 W, Max.

Current

  • RTD Excitation Current: 1-10 mA Depending on RTD Typical

Electrical Connectors

  • 8-Pin
  • Screw Terminal

Enclosure Finish

  • Urethane Coating

Linearity

  • AP4001 / AP4041 (Best Straight Line & Linear Input): 0.1 % of Span Typical (Referred to Resistance Input)

Mounting

  • DIN Rail
  • Mounting Holes
  • Track/Surface

Operating Temperature

  • 0° to 60° C (32° to 140° F)

Output

  • 0-10 V
  • 10 V Swing, Max.
  • 50 mA - Max.
  • AP4001 / AP4151: 4-50 mA
  • AP4041: ± 5 V
  • AP4041: 4-20 mA
  • Open Circuit Voltage: 30 V, Max.
  • Output Drive (Current): 15 V Compliance at 20 mA
  • Output Drive (Voltage): 10 mA - Max.
  • Output Ripple (24 Vdc Power): 0.5 % of Span, Max.
  • Output Ripple (24 Vdc Power): 10 mV RMS, whichever is greater
  • Output Ripple: 0.2 % of Span, Max.
  • Output Ripple: 5 mV RMS, whichever is greater

Output Impedence

  • Current: > 100 kiloohms
  • Voltage: < 10 ohms

Power

  • 120/240 Vac (± 10 %, 50/400 Hz)
  • Optional: ± 8 V, Inverter-Isolated (Mark II Case)
  • Optional: 24 Vdc

Resistance

  • Leadwire Resistance, Max.

Response Time

  • 100 milliseconds Typical

RTD Type

  • Cu10
  • Ni100
  • Ni120
  • Pt100
  • Pt200
  • Pt500

Span - Maximum

  • Output: 10 V
  • Output: 50 mA

Span - Minimum

  • Input RTD: ± [1° to 10° C (2° to 18° F)]
  • Output: 1 mA
  • Output: 100 mV

Span & Zero Adjustments

  • ± 10 % - Typical

Stability

  • ± 0.05 % of Span/°C Typical

Storage Temperature

  • -20° to 85° C (-4° to 185° F)

Temperature Range

  • Input RTD: -200° to 870° C (-328° to 1,600° F)

Voltage

  • Common Mode Voltage: 500 Vdc or Peak AC, Max.
show more