SW Solar Hybrid Inverter 120/240V
Brand: Schneider ElectricSW 120/240V hybrid inverter is perfect for off-grid, backup power, and self-consumption applications for homes and small businesses, it’s a pure sine wave, hybrid inverter system with switchable 50/60 Hz frequencies, providing power for every need.
SW features 120/240 VAC output, and capable of producing 120/240 VAC output from a 120 VAC input, without the need for an external transformer.
For expanded off-grid capacity, the SW is integrated with fuel-based generators as required to support loads larger than the generator’s output.
It’s also self-consumption ready, able to prioritize solar consumption over the grid while maintaining zero grid export.
SW hybrid inverter works with the grid to avoid peak utility charges and support the grid when utility supply is limited.
Specifications
Brand
Output Power (Continuous) at 25° C
- SW 4024 120/240: 3400 W
- SW 4048 120/240: 3800 W
Output Power (30 min) at 25° C
- SW 4024 120/240: 4000 W
- SW 4048 120/240: 4400 W
Output Power (5 sec) at 25° C
- SW 4024 120/240: 7000 W
- SW 4048 120/240: 7000 W
Peak Current
- SW 4024 120/240: 41 A
- SW 4048 120/240: 41 A
Output Frequency
- SW 4024 120/240: 50/60 Hz selectable
- SW 4048 120/240: 50/60 Hz selectable
Output Voltage
- SW 4024 120/240: 120 / 240 Vac
- SW 4048 120/240: 120 / 240 Vac
Output Wave form
- SW 4024 120/240: True sine wave
- SW 4048 120/240: True sine wave
Optimal Efficiency
- SW 4024 120/240: 92 %
- SW 4048 120/240: 94 %
Idle Consumption Search Mode
- SW 4024 120/240: < 11 W
- SW 4048 120/240: < 11 W
Input DC Voltage Range
- SW 4024 120/240: 20 - 34 Vdc
- SW 4048 120/240: 40 - 68 Vdc
AC Connections
- SW 4024 120/240: Single / Split phase
- SW 4048 120/240: Single / Split phase
Output Current
- SW 4024 120/240: 90 A
- SW 4048 120/240: 45 A
Nominal Output Voltage
- SW 4024 120/240: 24 Vdc
- SW 4048 120/240: 48 Vdc
Output Voltage Range
- SW 4024 120/240: 12 - 32 Vdc
- SW 4048 120/240: 24 - 64 Vdc
Charge Control
- SW 4024 120/240: 2 or 3 stage
- SW 4048 120/240: 2 or 3 stage
Charge Temperature Compensation
- SW 4024 120/240: Yes - BTS included
- SW 4048 120/240: Yes - BTS included
AC Input Power Factor
- SW 4024 120/240: > 0.98
- SW 4048 120/240: > 0.98
Input Current
- SW 4024 120/240: 13 A
- SW 4048 120/240: 12 A
Input AC Voltage
- SW 4024 120/240: 120 / 240 Vac split phase
- SW 4048 120/240: 120 / 240 Vac split phase
Input AC Voltage Range Line to Neutral
- SW 4024 120/240: 95 - 135 Vac single phase 170 - 270 Vac
- SW 4048 120/240: 95 - 135 Vac single phase 170 - 270 Vac
Dead Battery Charge
- SW 4024 120/240: Yes
- SW 4048 120/240: Yes
Tare Loss
- SW 4024 120/240: 29 W
- SW 4048 120/240: 27 W
Compatible Battery Types
- SW 4024 120/240: FLA, Gel, AGM, Custom
- SW 4048 120/240: FLA, Gel, AGM, Custom
Transfer Relay Rating
- SW 4024 120/240: 30 A
- SW 4048 120/240: 30 A
Transfer Time (AC to inverter and inverter to AC)
- SW 4024 120/240: < 1 cycle (16.7 millisecond)
- SW 4048 120/240: < 1 cycle (16.7 millisecond)
Optimal Operating Temperature Range
- SW 4024 120/240: -20° C to 60° C (-4° F to 140° F)
- SW 4048 120/240: -20° C to 60° C (-4° F to 140° F)
Storage Ambient Temperature Range
- SW 4024 120/240: -40° C to 85° C (-40° F to 185° F)
- SW 4048 120/240: -40° C to 85° C (-40° F to 185° F)
Humidity Operation / Storage
- SW 4024 120/240: < 95 % Relative Humidity, Non-Condensing
- SW 4048 120/240: < 95 % Relative Humidity, Non-Condensing
Ingress Protection Rating
- SW 4024 120/240: Indoor only, IP20
- SW 4048 120/240: Indoor only, IP20
Altitute (Operating)
- SW 4024 120/240: 2000 m (6562 ft)
- SW 4048 120/240: 2000 m (6562 ft)
Product Weight
- SW 4024 120/240: 28.1 kg (62.0 lb)
- SW 4048 120/240: 28.1 kg (62.0 lb)
Shipping Weight
- SW 4024 120/240: 35.0 kg (77.2 lb)
- SW 4048 120/240: 35.0 kg (77.2 lb)
Product Dimensions (H x W x D)
- SW 4024 120/240: 41.8 x 34.1 x 19.7 cm (16.5 x 13.4 x 7.6 in)
- SW 4048 120/240: 41.8 x 34.1 x 19.7 cm (16.5 x 13.4 x 7.6 in)
Shipping Dimensions (H x W x D)
- SW 4024 120/240: 56.0 x 44.0 x 32.0 cm (22.0 x 17.3 x 12.6 in)
- SW 4048 120/240: 56.0 x 44.0 x 32.0 cm (22.0 x 17.3 x 12.6 in)
System Network and Remote Monitoring
- Available
Safety
- c(CSA) us mark CSA C22.2, No. 107.1-01 UL 1741 Ed.2
EMC
- FCC Part 15 Class B
Power Distribution Panels
- Universal DC distribution panel (865-1016), AC distribution panel (120/240 V) (865-1017)
MPPT Charge Controllers
- MPPT 100 600 (865-1034), MPPT 80 600 (865-1032), MPPT 60 150 (865-1030-1)
Monitoring
- InsightHome (865-0330), InsightFacility (865-0335), Insight
Accessories
- Automatic Generator Start (865-1060-01), Battery Monitor (865-1080-01), Configuration Tool (865-1155-01)